Brand Name : Emerson
Model Number : KJ2005X1-MQ1
Certification : CE
Place of Origin : U.S.A / Thailand / UK
MOQ : 1
Price : Contact us
Payment Terms : T/T
Supply Ability : 50
Delivery Time : 3-5 work days
Packaging Details : New Original Box
Model : KJ2005X1-MQ1
Brand : Emerson DeltaV
Condition : NEW ORIGINAL
TYPE : Terminal Block
Weight : 4.3kg
Ambient Temperature : -40°C to +70°C
EMERSON VE3008 CE3008 KJ2005X1-MQ112P6381X042 Deltavim MQ Controller
VE3008 CE3008 KJ2005X1-MQ1 12P6381X042 DeltaV MQ Controller EMERSON
Manufacturers :EMERSON
Model(s):VE3008 CE3008 KJ2005X1-MQ1 12P6381X042Additional
Information : DeltaV™ MQ ControllerEstimated
Shipping Size
Dimensions:263x58 x28mm
Weight..4.3 kg
Country of Origin: United States of America
KJ2005X1-MQ1:
Power requirement: Supplied by System Power Supply through 2-wide Power/Controller Carrier
Fuse protection: 3.0 A, non-replaceable Fuses
Power dissipation: 5.0 W typical. 7.0 w maximum
Mounting: On right slot of power/controller carrier
User memory: 48 MB
Primary control network: 8-pin RJ-45 connector
Redundant control network: 8-pin RJ-45 connector
The KJ2005X1-MQ1 MQ Controller is a DeltaV scalable process system controller designed and certified for use in hazardous areas. It holds a Zone 2 rating, suitable for areas where flammable gases or vapors may occasionally occur during regular operations.
Power Supply Rating: +5 VDC at 1.4 A
Operating Temperature Range: -40 to 70 degrees Celsius
Environmental Endurance: Shock and vibration resistant, capable of withstanding airborne contaminants according to ISA-S71.04-1985 Airborne Contaminants Class G3.
The controller cannot be removed or inserted with system power energized.
It contains no user-serviceable parts and should not be disassembled under any circumstances.
Calibration is not required.
ATEX: II 3 G
FM: FM12ATEX0090U
IECEx: IECEx FMG 12.0035U
The KJ2005X1-MQ1 MQ Controller must be installed and used following the DeltaV ™ Scalable Process System Zone 2 Installation Instructions (document 12P2046). Additional installation guidelines are available in the “Installing Your DeltaV Automation System” manual.
The communications network connected to the DeltaV Controller should not be linked to a source that generates or contains, under normal conditions, a potential exceeding 60 VAC or 75 VDC.
The KJ2005X1-MQ1 MQ Controller does not contain user-serviceable parts and should not be disassembled. Calibration is unnecessary. If maintenance or adjustment is required, the controller must be returned to an authorized Emerson service center.
VE3008 KJ2005x1-MQ1 Features
Increases Productivity self-addressing, selflocating, automatic l/0 detection
Easy to use: total control, data protection, cold restart
Has the flexibility to meet your needs. data pass-through, prepares you for the future, mounting
Power Specifications
Local Bus Power +5 VDC at 1.4 A
Environmental Specifications
Ambient Temperature :-40°C to +70°C
Shock :10g ½ Sinewave for 11msec
Vibration: 1mm Peak to Peak from 2 to 13.2Hz; 0.7g from 13.2 to 150Hz
Airborne Contaminants: ISA-S71.04 –1985 Airborne Contaminants Class G3
Relative Humidity 5 to 95% Non-Condensing
Note: Refer to the product label for serial number and location and date of manufacture.
Warning: This product has specific instructions for installation, removal and operation in hazardous areas. Refer to document 12P2046 "DeltaV™ Scalable Process System Zone 2 Installation Instructions". Other installation instructions are available in the "DeltaV™ M-Series Hardware Installation and Reference" manual.
The communications network connected to the DeltaV Remote Interface Unit must not be connected to a source that generates or contains under normal conditions a potential in excess of 60 VAC or 75 VDC.
![]() |
EMERSON VE3008 CE3008 KJ2005X1-MQ112P6381X042 Deltavim MQ Controller Images |